18 Years Factory Steam Pressure Transmitter Rs485 - Online Conductivity Transmitter With Sensor – JIRS Detail:
Code: BSQ-EC-2019
General introduction
EC/ER/pH/ORP-2019 series transmitter mainly used for the water quality monitor sensor signal output, by 4-20mA, RS485 or TTL, the sensor output weak signal is enlarged to transmit, can be convenient for PLC, configuration software and SCM to communicate by adopting standard communication protocol MODBUS protocol.
EC/ER/pH/ORP series transmitter is widely used in metallurgy manufacturing, power, light industry, textile, water treatment equipment, water pipe network and the scientific research and other industrial sectors.
Transmitter series introduction
Note: A module of the transmitter can only be equipped with one sensor, EC/ER is a module, and PH / ORP is a module.
①: EC conductivity transmitter; range: 0 ~ 4000us / cm, 0-10/20/200mS
②: ER resistivity transmitter; range: 0 ~ 18.2MΩ
③: pH transmitter; range: 0 ~ 14.00 pH
④: ORP redox potential transmitter; range: -2000 ~ + 2000mV
Transmitter series technique specification
No. |
Range |
Matched sensor |
Accuracy |
Connection |
1 |
0.1~18.25MΩ 0.05~10.00uS) |
1:316L S.S. plug into 0.01 sensor 2:Quick install 0.02 sensor; |
2 %FS |
1/2″NPT 1/4”Quick install |
2 |
0.1~200.0uS |
316L S.S. plug-into 0.1 sensor |
|
1/2″NPT) |
3 |
0.5~2000uS(standard) |
ABS1.0 Pt. Black sensor(standard) 316L S.S. plug into 1.0 sensor |
1.5% FS |
1/2″NPT
|
4 |
2~4000uS |
ABS1.0 Pt. Black sensor(standard) 316L S.S. plug into 1.0 sensor |
1.5% FS |
1/2″NPT
|
5 |
0.5~10mS |
ABS1.0 Pt. Black sensor(standard) 316L S.S. plug into 1.0 sensor |
3 % FS |
1/2″NPT
|
6 |
0.5~20mS |
1:316LS.S. plug into10.0 (standard) 2:PTFE+Titanium alloy 10.0 sensor |
1.5 % FS |
1/2″NPT 3/4″NPT |
7 |
0.5~100mS |
1:316LS.S. plug into10.0 (standard) 2:PTFE+Titanium alloy 10.0 sensor |
2 % FS |
1/2″NPT 3/4″NPT |
8 |
0.5~200mS |
PTFE+Titanium alloy 10.0 sensor |
2 % FS |
3/4″NPT |
EC- Conductivity transmitter technique specification,
●Stability: ±2×10-3FS/24h,
●Sensor: 1.0cm-1 constant ABS engineering Plastic Pt. Black sensor, Plug-in or quick-install optional ( other 10.0cm-1 constant sensor optional),
●Sensor threaded size: 1/2″NPT,
●Cable length: Plug-in type standard length is 5m, Quick mounted type is 1.5m,
Measured media temperature:0~50℃,
●Sensor working pressure: 0-0.5Mpa,
●Temperature sensor: NTC 10K,
●Temp. compensation: On basis of 25℃, Auto temp. Compensation.
Other common technique specification,
●Output current: 4~20mA, isolated / Optional:1-5V /2-10V
●Relay output: High/Low limit relay alarm output, Contact point current 24V/3A, 220V/2A ( Passive dry contact)
●Power: DC12V-28V, 24V(Current <=0.1A)
●Environmental conditions: Working temperature:0~50℃, Relative humidity: ≤ 85%RH
●Overall dimension: 122×72×45mm(L x W x H),Installation mode: Cabinet rail installation
Product detail pictures:
Related Product Guide:
We've numerous great employees customers excellent at promoting, QC, and working with kinds of troublesome difficulty inside the generation method for 18 Years Factory Steam Pressure Transmitter Rs485 - Online Conductivity Transmitter With Sensor – JIRS , The product will supply to all over the world, such as: Mecca, Berlin, Sri Lanka, Our aim is to help customers realize their goals. We have been making great efforts to achieve this win-win situation and sincerely welcome you to join us. In a word, when you choose us, you choose a perfect life. Welcome to visit our factory and welcome your order! For further inquiries, you should do not hesitate to contact us.
By Aaron from San Francisco - 2017.06.22 12:49
We have worked with many companies, but this time is the best,detailed explanation, timely delivery and quality qualified, nice!
By Elvira from Paris - 2018.09.12 17:18